Emerson Process Management ROSEMOUNT 5300 Bedienungsanleitung Seite 134

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 324
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 133
Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
7-4
Surface Threshold - amplitude threshold for detection of the Product level
peak. The surface threshold is designed as a number of individually
adjustable amplitude threshold points, the Amplitude Threshold Curve (ATC),
see “Amplitude Threshold Curve” on page 7-7.
Interface Threshold - amplitude threshold for detection of the Interface level
peak.
Full Tank Threshold - amplitude threshold that can be used to detect
whether the probe is fully submerged in the upper product or not.
Probe End Threshold - amplitude threshold for detection of the Probe End
peak.
Thresholds are recommended to be set to approximately 50% of the signal
peak amplitude. To adjust the Amplitude Thresholds see “Using the Echo
Curve Analyzer” on page 7-10.
Seitenansicht 133
1 2 ... 129 130 131 132 133 134 135 136 137 138 139 ... 323 324

Kommentare zu diesen Handbüchern

Keine Kommentare